For Virginia Tech's Blacksburg campus:

Ground Snow Load
30 psf

Wind Exposure
Category B (unless otherwise determined by actual site conditions)

Seismic Zone
2

Spectral Response Acceleration

  • Ss%g: 28% (unless otherwise determined by actual site conditions)
  • S1%g: 7% (unless otherwise determined by actual site conditions)

Subject to Damage from

  • Weathering: Severe
  • Frost Depth: 24” min.
  • Termite: Moderate to heavy
  • Decay: Slight to Moderate

Ice Shield Required
Yes

Flood Hazard
Some areas yes; refer to Flood Insurance Rate Maps (FIRM) for more information

Climate Zone
4

Winter Design Temperature
16 F

Yearly Heating Days
4150

Yearly Cooling Days
1154

Mean Annual temperature
55 F

Air Freezing Index
250

Latitude/Longitude
37° 13’ 38.94” N / 80° 25’ 19.70” W

For additional information, contact the Office of the University Building Official at 540-231-5534.

Contact the Office of the University Building Official

Chris Kiel
University Building Official
ckiel@vt.edu
540-231-4678

David S. Brown
Building Code Plan Reviewer/Inspector
davidsb22@vt.edu
540-204-5250

John Bush
Architect
bushj@vt.edu
540-598-0392

Marie Castillo
Assistant Permit Technician
mdotson@vt.edu
540-231-2414

Christopher McGrath
Building Code Plan Reviewer/Inspector
cmcgrath@vt.edu
540-835-4821

Gerald Smith
Assistant Permit Technician
geraldws@vt.edu
540-774-6724

Steve Smith
Building Code Plan Reviewer/Inspector
stsmith1@vt.edu
540-553-1929

Heather Snidow
Permit Technician/Administrative Coordinator
hsnidow@vt.edu
540-231-5534

Jack Thompson, Jr.
Building Code Plan Reviewer/Inspector
jlthomps@vt.edu
540-739-0129