Building Code-Related Design Criteria
For Virginia Tech's Blacksburg campus:
Ground Snow Load
30 psf
Wind Exposure
Category B (unless otherwise determined by actual site conditions)
Seismic Zone
2
Spectral Response Acceleration
- Ss%g: 28% (unless otherwise determined by actual site conditions)
- S1%g: 7% (unless otherwise determined by actual site conditions)
Subject to Damage from
- Weathering: Severe
- Frost Depth: 24” min.
- Termite: Moderate to heavy
- Decay: Slight to Moderate
Ice Shield Required
Yes
Flood Hazard
Some areas yes; refer to Flood Insurance Rate Maps (FIRM) for more information
Climate Zone
4
Winter Design Temperature
16 F
Yearly Heating Days
4150
Yearly Cooling Days
1154
Mean Annual temperature
55 F
Air Freezing Index
250
Latitude/Longitude
37° 13’ 38.94” N / 80° 25’ 19.70” W
For additional information, contact the Office of the University Building Official at 540-231-5534.